Model Number | PRO2 |
Product Name | Server Technology PRO2 Expansion PDU |
Product Type | PDU |
Features | |
HDOT Cx Outlets | Cx is the future-ready UL tested hybrid of a C13 and C19 outlet accommodating both C14 and C20 plugs. |
Hot-Swap Network Card | Network access is ensured when power is lost to the Primary unit with backup power provided by the Linked unit. |
Temperature/Humidity Monitoring | Supports two external 10' (3m) T/H probes. Receive SNMP-based alerts and email notifications. |
Auto-Flip Current Display | Easy-to-read LEDs display current per phase to help prevent overloads and simplify three-phase load balancing in high density cabinets. |
Per-Outlet Power Sensing | POPS (Per Outlet Power Sensing) Monitors Current Load (A), Voltage (V), Power (W), Apparent Power (VA), Crest Factor, Power Factor, and Energy per outlet. |
Branch Circuit Protection | This PDU meets the UL and IEC 62368-1 requirement for branch circuit protection through UL 489 rated magnetic hydraulic circuit breakers or UL 248 fuses. |
Alternating-Phase Outlets | Evenly distributes multiple phases of power to each outlet for simplified load balancing, reduced cord lengths, and better airflow. |
High Temperature Rating | This product has been tested and approved for safe and reliable operation in 60 C data center environments. |
Color-Coded Options | Select from six colors to designate PDU circuits in the data center black, white, red, green, blue, and yellow. |
Network Monitoring | Gain access to valuable data through connections including HTTP(S), SSH, Telnet, SNMP, (S)FTP, SMTP, Syslog, LDAP(S), RS-232 serial, and more. |
Star Multi-Linking | PRO2 provides the ability to link up to four power circuits using one IP address. |
IP Access, Security & Communications | Web, SSH, Telnet, SNMPv2c & v3, RS-232 serial, 10/100 Base T-Ethernet, LDAP(S), TACACS+, RADIUS, DHCP, & SMTP/email. |
Per-Inlet Power Sensing | PIPS (Per Inlet Power Sensing) Monitors Current Load (A), Voltage (V), Power (W), Apparent Power (VA), Crest Factor, Power Factor, & Energy per inlet. |
Branch Current Monitoring | Monitors current at each breaker branch and provides SNMP based alerts and emails on high usage that risks a tripped circuit. |
Outlet Control | On Switched PDUs, cycle power to individual outlets or groups of outlets to reboot servers, or power off unused receptacles. |
High Retention Locking Outlets | PRO2 receptacles have high retention and are compatible with P-Lock type power cords. |
Flexible Mounting | Includes standard button mounts along with provisions for custom mounting brackets. |
Inputs | |
Input Voltage (V) | 208 |
Frequency | 50/60 Hz |
Input Plug | 208V Delta 60A IEC 60309 3P+G 9Hr |
Input Current (A) | 60 |
Input Current Rated (A) | 48 |
Input Power Capacity (kW) | 17.3 |
Outputs | |
Connector | Rating |
(24) x IEC 60320/C13 North American Rating | 12A @208V L-L (15A Peak) |
(12) x Cx North American Rating | 16A @208V L-L (20A Peak) |
Specifications | |
Branch Circuit Protection | UL 489, CSA C22.2 No. 5 & IEC/EN60947-2 Compliant 2-pole, 20A trip circuit breakers, six (6) branch, rating: 16A, 10 kAIC Interrupt Rating |
Physical | Dimensions: 70.0in tall x 2.2in wide x 2.5in deep [1778mm x 56mm x 64mm] |
Environmental | Operating Environment: 32F to 140F / 0C to 60C |
Communications & Security | 10/100 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector) |
Certifications | North American: |
Measurement Accuracy | Input Measurement Accuracy: |
Output Measurement Accuracy | GUI Current = 1% at 0.01 amp resolution (above 0.15 amp) |
Branch Measurement Accuracy | Current = 3% at 0.01 amp resolution (above 0.5 amp) |
Warranty | |