Contact Us
Sales: 1.866.880.1230 Operating Hours Monday — Friday |
|
General | |
Model number | C2S36TE-2CAF2M99 |
Product Name | Server Technology C2S36TE-2CAF2M99 Smart Master Pro2 Hdot Outlets |
Product Type | Hdot Outlets |
Input Voltage | 208 V |
Input Plug Type | NEMA L6-30P |
Input Current | 30 A |
Input Current Rated | 24 A |
Input Power Capacity | 5 KW |
Connector | (18) x IEC 60320/C13: North American Rating: ? 12A @208V L-L (15A Peak); (18) x Cx: North American Rating: ? 16A @208V L-L (20A Peak) |
Operating Environment | 32degF to 140degF / 0degC to 60degC |
Storage Environment | -40degF to 185degF / -40degC to 85degC |
Communications & Security | 10/100/1000 Mbps Ethernet (RJ-45 connector), RS-232 serial (RJ-45 connector); Two (2) temperature/humidity sensor inputs (4P4C), Link port (RJ-12) - {also on Link PDU}; Web-browser GUI and command-line interface (CLI): HTTP/HTTPS, TLSv1.2, SSHv2, Telnet, SNMPv2c and v3 (GET, SET, Traps), IPv4 and IPv6, LDAPv3/LDAPS, TACACS+, RADIUS, FTP/SFTP |
LED Current | +- 10% at 0.1 amp (0.3 - 9.9 amps) and 1 amp (> 9.9 amps) resolution |
GUI Current | +- 1% at 0.01 amp resolution (above 0.25 amp) |
Voltage | 1% at 0.1 volt resolution (nominal +- 10%) |
Active Power | +- 1% at 1 watt resolution |
Apparent Power | +- 1% at 1 volt-amp resolution |
Power Factor | +- 3% at 0.01 resolution |
Crest Factor | +- 10% at 0.1 resolution |
Energy | +- 1% at 0.1 kilowatt-hour resolution |
Branch Measurement Accuracy | Current = +- 3% at 0.01 amp resolution (above 0.5 amp) |
Branch Circuit Protection | UL489 Compliant 2-pole, 20A trip circuit breakers, three (3) branch, rating: ? 16A, 10 kAIC Interrupt Rating |
Dimensions | 70 tall x 2.2 wide x 2.5 deep inches / [1778mm x 56mm x 64mm |
Warranty | |
Warranty: | Manufacturer Warranty. For defective returns, Tech For Less will give you a full refund and will arrange for and pay all shipping costs. |